filtration on sediment filters: cascade filtration on 20µm and 5µm high efficiency sediment filters,
filtration on carbon filters: filtration on granular activated carbon to remove organic compounds, chlorine and chlorine derivatives,
softening process (option): automatic softening station – rinsing and regeneration of the bed is carried out automatically, compact construction – corrosion resistant ion exchange column (fiberglass tank) placed inside the salt casing, high capacity for removing hardness ions,
reverse osmosis station: efficiency: 400 – 600 dm3 / h (depending on the model), retention ratio 96-99%, recovery rate 60%, high pressure pump, retentate and permeate rotameters,
UV lamp (option).
Automatic and maintenance-free operation of the device.
Retention rate is 96-99%.
Water intake point – third * purity class according to ISO 3696: 1999.
Tank for storing purified water (capacity to choose).
Automatic system shutdown when the tank is full or the water intake is closed.
Can be connected to a dishwasher, autoclave, analyzer, etc.
Possibility of creating a water distribution network with intake points covering several rooms or floors in a building.
Control water intake points.
Automatic membrane rinsing (possibility of individual setting of the period and time of membrane rinsing).
Forced flushing of membranes (service).
System designed for cold water supply: 5-40 ° C.
Possibility of self service by the User (without having to call the service).
Power supply: 230V / 50Hz.
Stainless steel frame.
Functions monitoring system operation:
The device is equipped with a microprocessor control and measuring system having:
color graphic display with Touch Panel function,
conductivity meter measuring the conductivity and temperature of tap water,
conductivity meter measuring the conductivity and temperature of purified water after reverse osmosis,
conductivity measurement in µS / cm or MOhm units,
automatic temperature compensation,
continuous control and preview of the degree of retention (degree of retention) of RO membranes,
clock displaying date and time,
alarm informing about mechanical and carbon filter replacement,
alarm informing about replacement of the RO module,
alarm informing about the UV lamp radiator replacement (option),
information about the tank filling level on the device display,
preview of service dates,
menu in Polish, English, Russian or Spain on display,
built-in RS 232 interface for communication with a computer ensuring the possibility of individual adjustment of service frequency and alarm levels,
built-in USB connector for communication with a computer ensuring the possibility of individual adjustment of service frequency and alarm levels,
computer program enabling individual settings of alarm thresholds and data archiving,
built-in manometer.
Functions securing the system operation:
Interruption of system operation with:
low feed water pressure (no feed water),
a full tank / closed water intake point.
Thermal protection of the osmotic module, automatic stopping of the system operation at the supply water temperature below 40C or above 400C.
Ability to stop the system when any alarm occurs.
System autostart capability.
Preview of monitoring messages / alarms.
Purified water in the device meets the requirements of ISO 3696: 1999 for waters of the third * degree of purity. * depends on the quality of the feed water, the degree of retention is 96-99%
Additional equipment / services:
tank for storing purified water:
pressure – option: 80 l, 110 l, 230 l, 320 l or 450 l,
pressureless – capacity to be agreed (on request),
compact device housing made of stainless acid-resistant steel (all system components, except for the tank, installed inside the housing),
automatic softening station,
tank housing made of stainless acid-resistant steel,
full DQ, IQ, OQ, PQ qualification procedure with documentation,
cooperation with building management systems (BMS).